Lighting recommendation for di erent areas - as per CIE - 129- 1998,
                          CIE S 015/E: 2005 & other Indian standards
 GENERAL AREA LIGHTING

                                                                          Maintained Average
                           Sr.             Typical Locations              Illuminance level (in lux)  Uniformity Ratio
                           No.                                            (E  )                      (E min /E avg  )
                                                                            avg
                             1   INDUSTRIAL YARDS & STORAGE AREAS
                                 Container Terminals (Short Term Handling)         20                     0.25

 Facade Lighting  Area Lighting  Parking Area  Container Terminals (Continuous Handling)  50              0.40

                                 Vehicle Parking Area                              20                     0.25
                                 Vehicle Tra c Area (Internal Roads)               20                     0.40



 Playground  Warehouse  Townships
                             2   PARKING LOTS
                                 Light Tra c Parking Lots                           5                     0.25

                                 Medium Tra c Parking Lots                         10                     0.25

                                 Heavy Tra c Parking Lots                          20                     0.25



                             3   PETROCHEMICAL INDUSTRIES & OTHER HAZARDOUS INDUSTRIES

                                 Tank Farm Area                                    20                     0.25

                                 Valve Area & Manifold                            50-60                   0.40
                                 Pump House & TLF Platform                         100                    0.40

                                 Vehicle Parking Area                              20                     0.25

                                 Vehicle Tra c Area (Internal Roads)               20                     0.40

                             4   POWER, ELECTRICITY, GAS & HEAT PLANTS
                                 Coal Handling Area                                20                     0.25

                                 Switch Yard Area                                  20                     0.25
                                 Switch Yard Area (Equipment Level)                50                     0.25/0.40

                                 Vehicle Parking Area                              20                     0.25

                                 Vehicle Tra c Area (Internal Roads)               20                     0.40

                                 Railway Yards                                     100                    0.25